http://www.kadhoai.com.cn 2026-04-08 04:43:55 來源:威圖電子機械技術(上海)有限公司
在(zai)控(kong)製(zhi)和(he)電(dian)氣(qi)櫃(gui)中(zhong),空(kong)調(tiao)不(bu)甚(shen)起(qi)眼(yan),但(dan)扮(ban)演(yan)著(zhe)至(zhi)關(guan)重(zhong)要(yao)的(de)作(zuo)用(yong),溫(wen)度(du)控(kong)製(zhi)對(dui)於(yu)電(dian)氣(qi)櫃(gui)中(zhong)的(de)電(dian)子(zi)電(dian)氣(qi)部(bu)件(jian)的(de)穩(wen)定(ding)運(yun)行(xing)至(zhi)關(guan)重(zhong)要(yao),特(te)別(bie)是(shi)在(zai)變(bian)頻(pin)櫃(gui)、啟(qi)動(dong)櫃(gui)中(zhong)或(huo)者(zhe)高(gao)溫(wen)運(yun)行(xing)的(de)場(chang)合(he)。空(kong)調(tiao)本(ben)身(shen)起(qi)著(zhe)調(tiao)節(jie)櫃(gui)內(nei)溫(wen)度(du)的(de)作(zuo)用(yong),它(ta)不(bu)能(neng)頻(pin)繁(fan)發(fa)生(sheng)故(gu)障(zhang),即(ji)使(shi)故(gu)障(zhang)發(fa)生(sheng),如(ru)果(guo)能(neng)夠(gou)及(ji)時(shi)報(bao)警(jing),甚(shen)至(zhi)在(zai)故(gu)障(zhang)發(fa)生(sheng)前(qian)能(neng)給(gei)運(yun)維(wei)人(ren)員(yuan)及(ji)時(shi)預(yu)警(jing)提(ti)醒(xing),使(shi)之(zhi)能(neng)達(da)到(dao)智(zhi)能(neng)的(de)預(yu)測(ce)性(xing)運(yun)維(wei),這(zhe)樣(yang)就(jiu)會(hui)大(da)量(liang)減(jian)少(shao)現(xian)場(chang)的(de)損(sun)失(shi)。

威圖Blue e+空調
威圖公司通過持續不斷的對市場上安裝運行的20萬台機櫃空調進行大數據分析,發現空調在客戶端實際應用過程中的主要問題有下麵幾種:
主要問題
1.缺乏保養,導致空調過濾網堵塞,進而空調停止運行或者導致銅管斷裂、壓縮機損害等二次故障。
2.空調的運行環境溫度太高。如某鋁廠的行車上,空調的運行溫度在60度左右,而夏天鋁廠行車電氣櫃環境溫度有時會更高,這樣就會造成空調宕機,給行車運行以及鋁廠的安全生產帶來極大的安全隱患。
3.空調三相電源接反,如果空調不帶有相序保護功能,會導致空調電路板燒掉。
4.空調能耗過高, 空調是車間的高耗能單元,對於工廠的降本增效有巨大的改善空間。
5.排水管堵塞或過長導致空調冷凝水漏水,進而會造成櫃內的電氣回路短路風險。
6.jiguimifengbuhao,daozhikongtiaochanshengdaliangdelengningshui,lengningshuiruguozaifengyaguodadechanghehuichanshengfeishui,zaiguineijiqirongyichanshengdianqihuiluduanlu,fashenghuozaihetingjifengxian。
7.機櫃內某處熱點溫度過高,導致熱點及周邊熱量聚集引起設備或元器件故障。